Conductor Sizing

Ampacity & Voltage Drop

1Code & voltage class

Voltage class
LV: NEC Table 310.16/310.17 · CEC Tables 1-4 (scoped 0-5 kV). Ampacity here is thermal - voltage doesn't change LV table values.

2Circuit

Load current (A)
System voltage (V)
One-way length (m)
Length never changes ampacity - it drives the voltage drop check. Set 0 to skip.
System

3Conductor

Material
Parallel sets per phase (310.10(G) / 12-108: min 1/0; max 12 here)
Insulation rating (TW · RW75 · RW90/TECK90)
Termination rating (110.14(C) / 4-006)

4Installation conditions

Ambient temperature (°C)
Other circuits sharing this raceway
CCC is derived automatically: phases (+ neutral if toggled) × sets in this raceway, plus the same per circuit added. Derived total appears in the calculation trace.

5Voltage drop

CEC 8-102: 3% in a feeder or branch circuit, 5% total from service to point of use (mandatory). With a length entered, VD is always reported; the toggle controls whether the conductor is upsized to meet the limit.
VD limit
Power factor (0.1-1)
Disclaimer and reference standards

Engineering aid - verify before use. Results are not a stamped design. The engineer of record is responsible for the final selection, and no warranty is expressed or implied.

LV ampacity: NEC 2023 Table 310.16 (raceway/cable/earth) and 310.17 (free air); CEC Tables 1-4. The two sets have been harmonized since 2012 but remain independently published - check both if cross-referencing.

LV underground: CEC uses CSA C22.1:21 Appendix D, Tables D8A-D11B (Diagrams D8-D11). Those are three-phase arrangements - every column is "n cables per phase" and each table's Note 1 bounds it at three current-carrying conductors - so a 2-wire single-phase run is sized on Tables 2/4 with the Table 5A/5C factors instead. NEC uses Informative Annex B, Table B.2(10) Details 9/10 (directly buried) and Table B.2(7) Details 1-3 (duct bank). Annex B is informative; the mandatory NEC basis is Table 310.16.

MV ampacity: NEC 2023 Tables 315.60(C)(1)-(20) - the complete set covering single conductors, triplexed assemblies, and three-conductor cable, installed in free air, in conduit in air, in underground ducts, or directly buried. Ampacities assume shields grounded at one point. Only single conductors isolated in air are tabulated above 35 kV.

Termination temperature: CEC Rule 4-006 / NEC 110.14(C) - the usable column is set by the lowest-rated termination in the circuit.

Bonding / EGC: CEC Table 16; NEC Table 250.122.

Voltage drop: CEC Rule 8-102 with Appendix D Table D3 (CSA C22.1:24 - K in Ω/circuit-km, Raceway column, pf-interpolated between the published 80%/90% columns, Note 3 temperature correction, Note 2 published f factor: 1.73 for 3-phase line-to-line, 2 otherwise). NEC Chapter 9 Table 9 alternating-current resistance and reactance, with separate steel-raceway columns. Table 8 (DC) is used only where Table 9 has no row, and is labelled when it is.

Overcurrent protection: CEC Rule 14-104 with Table 13; NEC 240.4(B), 240.4(D) and 240.6(A).